37 kVA SuperSilenced Biodiesel Generator

GENERATOR - SKID

  • Heavy Duty Construction
  • Lightweight and Compact Design
  • Super-Silent operation 54 dBA
  • Tier 2 Diesel Isuzu Engine
  • 100% Biodiesel Compatible
  • Back to Base Monitoring
  • Solar & Battery "Hybrid" Ready
  • Battery Isolator
  • Emergency Stop
  • Two Way Auxiliary Tank Valve
  • Bunded base tank with fork pockets

Exceptionally quiet operation and a economical Tier 2 Isuzu Diesel engine makes this 37  kVA portable Diesel Generator a main stay of many hire fleets around Australia. Comes complete with 3 x 3 Phase IP66 plugs from the factory and standard mine features such as battery isolator and emergency stop from the factory.

GPS SuperSilenced biodiesel generators combine design simplicity with uncompromising standards of engineering and manufacturing excellence they are lightweight with a compact footprint. All engines meet current EPA emission standards. Durable all-weather outer enclosure with powder coated exterior and stainless steel fasteners throughout provide protection against corrosion.

Specifications

Alternator
Rated Output37 kVA, 29.6 KW
Frequency50 Hz
Rated Voltage240 Volts
Rated Current51 Amps
Number of Poles4 Poles, 20 Amp
Rated Power Factor0.8 (Lagging)
Engine
ModelIsuzu 4GJIT
Emission RatingTier 2
Air Induction SystemTurbocharged
Number of Cylinders4
Bore and Stroke95.4 mm x 107 mm
Displacement3.059 Litres
Rated Output35.4 KW
Rated Speed1,500 RPM
FuelDiesel - Biodiesel
Fuel Tank Capacity124 Litres
Fuel Tank Capacity (Base tank)245 Litres
Lubrication Volume10 Litres
Physical Characteristics
DimensionsL 1770 mm x W 920 mm x H 1350 mm
Dimensions (with Base tank)L 1770 mm x W 920 mm x H 1700 mm
Dry Weight1140 Kg
Wet Weight1420 Kg
Wet Weight (with Base tank)1650 Kg
Sound Level @ 7 meters54 dBA
Controls & connections:
ControllerDeepsea DSE8610
Communications ModuleDeepsea DSE890
Start and StopManual or Automatic scheduling
WarningsBattery Charge with lamp indication
ShutdownsOil Pressure & Water Temperature

Performance Details

Fuel consumption @ 25% load3.9 Litres per Hour
Fuel consumption @ 50% load5.0 Litres per Hour
Fuel consumption @ 75% load6.6 Litres per Hour
Fuel consumption @ 100% load7.8 Litres per Hour
SynchronisableYes
Hybrid compatibilitySolar - Battery
Auxiliary tank2,000 Litre
Maintenance and Fuel schedulingB2B Automatic booking